PRODUCT

ENTERPRISE BRIEF INTRODUCTION

HKJY - E DC Insulation Detecting Device

Application Scenarios:Used in direct current application field,such as photovoltaic generation area,electric mobile recharging pile,etc.

PRODUCT OVERVIEW

Mainly used to monitor the insulation status of the IT system (ungrounded system) to the ground,it can detect the insulation resistance value of the positive and negative poles of the DC floating system to the ground.and to alarm in time when the system has an insulation fault to remind the electrical maintenance personnel to troubleshoot the fault.

 

KEY FEATURE

  • RS 485 communication

  • Relay output

  • Monitoring and protection function

  • Alarm function

   Parameter

data

condition

Voltage measurement range

0~500V

Rated voltage 500V series

0~1000V

Rated voltage 1000V series

0~1500V

Rated voltage 1500V series

Grounded

insulation

Working:0.5MQ, when stopping measurement >300M

Rated voltage 500V series

Working: 1MQ,  when stopping measurement >300M

Rated voltage 1000V series

Working:1.5MQ, when stopping measurement >300M 

Rated voltage 1500V series

accuracy

0.5%(quoted error)

 

APS voltage

24V±10%

 

APS power

<3W

 

 

Alarm relay touch point

Long term connection3A,

Disconnect:250VDC r=5ms 25W DC inductive load

Disconnect 250VAC COSD=0.4100VA AC load

Resistive load:3A,30V DC

Resistive load:3A,250V AC

 

 

 

Insulation

Resistance

R+、R

accuracy

(R+、R- difference multiple<5 times)①

Insulation range

cY②capacitance range

voltage

≤3k Q

≤60kQ

 

0~0.8μF

 

 

100%

PH

40%

5%

60kQ^1MQ

10%

1MQ~50MQ

≤6k  Ω

≤60kΩ

0.8μF~3

u F

20%

60kΩ^1MQ

30%

1M2~50M2

      Installation size & wireing 

       

Terminal code

Function

Code

 Function

 Defining

 

Terminal Code

Function

Code

Function

defining

1

DC bus line

  Negative end

Connect with DC

 Bus lince negative end

10

A

RS485

2、3、4

impendence

 

11

B

5

ground

grounded

12

R

Short connect

R f& S

Stop measuring insulation resistance

6、7、8

impendence

 

13

S

9

DC bus line

Positive end

Connect with DC bus line positive end

14、15、16

 

Alarm relay

touch point

 

 

 

17

APS negative

end

APS

 

 

 

18

APS positive

end

 

HKJY - E DC Insulation Detecting Device

Baidu
sogou