PRODUCT

ENTERPRISE BRIEF INTRODUCTION

Commodity: HK-ESGU Energy Storage Unit Controller

Product Overview:

HK-ESG As the connection bridge between EMS and energy storage units,HK--ESGU connects EMS upwards through LAN interfaces,connects PCS downwards through Ether CAT,real-time bus for real-time power control collects and stores data including but not limited to:battery information,distribution switch status,comprehensive protection information,transformer,fire protection and other dynamic  environment  Information,other instrument information,etc,and uploads EMS to the bus.HK-ESGU collects all PCS data in the aggregation group and combines them into a single PCS according to the relevant conversion basis model,upload the status of the energy storage unit to the EMS in a single PCS state quantity.HK-ESGU receives the EMS master modulation,and at the same time allocates the active and reactive power regulation of each PCS in real time according to the collected PCS and BMS information,and then distributes the regulation of teach PCS to each PCS at the same time.

Key Feature:

  • Realize 64 nodes communication cycle 1ms accurate control
  • Power dispatching corresponding time  < 1 0ms
  • Clock jitter control. Realize 300nodes,15ms synchronous error,±20ms synchronous jitter
  • High integration of system energy flow and data flow,output in one bus

Data Sampling

AC Current

Sampling Accuracy

/

0.2%

Channel Number

/

≥6

AC Voltage

Sampling Accuracy

 

0.2%

Channel Number

 

≥6

Analog Value Input

(4mA-20mA)

 Sampling Accuracy

0.1%

0.1%

 Channel Number

≥6

≥6

Power Measurement Accuracy

/

0.5%

Frequency Measurement Accuracy

 

0.005Hz

Digital Value Input DI Quantity

Optional

Optional

Touch Point Output (DO passive node) Quantity

Optional

Optional

Communication Cycle

64 sets PCS 1ms

64sets ESGU 1ms

Synchronous Jitter

<1μs

<1μs

Control Order Time Accuracy

Frequency adjustment action time

 

≤20ms

Dynamic reactive voltage

Adjustment action time

/

≤10ms

AGC/AVC Adjustment order

 Action time

≤10ms

≤10ms

Master\spare machine cut time

/

≤10ms

Communication Interface

LAN/CAN/RS485/USB

Communicate with CCU/EMS

Communication Protocol

IEC104/Modbus(TCP, RTU)/IEC61850/EtherCAT

Interface type & quantity

2 ways

2ways

Communicate with PCS/ESGU

 Communication protocol

EtherCAT

EtherCAT

Interface type & quantity

2 ways

2ways

Local Monitor System Size

13.1 inch

13.1 inch

Main Control Cabinet Size

600*600*1600mm 

800*600*1600mm

Control Power Supply Size

220V*3A

220V*5A

 

HK-ESGU Energy Storage Unit Controller

Baidu
sogou